BNET ERVITAL FIRE SAFE STANDARD CABLE 2X1.5 MM2 SOLID RED LSZH LPCB APPROVED 500M DRUM MADE IN TURKEY
FLAME RETARDANT CHARACTERISTIC / LOW SMOKE EMISSION / WITHOUT POISONED AND CORROSIVE GASSES / CIRCUIT INTEGRITY 180 MINUTES / CIRCUIT INTEGRITY WITH SHOCK PH 120 / CWZ ACCORDING TO BS STANDARDS
|
BEFSC500MRE2150R |
BNET ERVITAL FIRE SAFE STANDARD CABLE 2X1.5 MM2 |
1 |
Conductor |
EN 60228
Class 1 (RE) |
2 |
Insulation |
EN 50363-1
EI2 Cross-linked Ceramic Forming Polymer Compound |
3 |
Insulation Colour |
2-core :
Brown, Blue 3-core :
Brown, Black, Grey 4-core :
Blue, Brown, Black, Grey |
4 |
Stranding |
In Layers Of
Optimum Pitch |
5 |
Wrapping |
Pes Tape |
6 |
Overall
Screen |
Tinned Copper
Drain Wire + Al-Pes Tape |
7 |
Sheath |
EN 50290-2-27
HFFR Compound |
8 |
Sheath Colour |
RAL 3000 Red |
9 |
Min.Bending
Radius |
6 x D |
10 |
Operating
Voltage |
300/500V |
11 |
Test Voltage (Core/Core-Core/Screen) |
2000V 30°C ~ +70°C
(Temp. for stationary condition ) |
12 |
Temperature
Range |
- 5°C ~ +50°C
(Temp. for moving condition ) +90°C (Max.Permissible Operating Temperature
at Conductor) |
13 |
Flame
Retardant Test |
IEC
60332-1-2, VDE 0482-332-1-2, EN 60332-1-2 |
14 |
Flame
Propagation Test(Cat C) |
IEC
60332-3-24, VDE 0482-332-3-24, EN 60332-3-24 |
15 |
Smoke Density
Test |
IEC 61034-2,
VDE 0482-1034-2, EN 61034-2 |
16 |
Corrosive Gas
Test |
IEC 60754-2,
VDE 0482-267-2-3, EN 50267-2-3 |
17 |
Halogen Free
Test |
IEC 60754-1,
VDE 0482-267-2-1, EN 50267-2-1 |
18 |
Circuit
Integrity With Shock and Water Test (C,W,Z) |
BS 6387: 2013 (Cat.C Fire 950⁰C) |
19 |
Circuit
Integrity Test (FE180) |
IEC 60331-21 |
20 |
Circuit
Integrity With ShockTest (PH120) |
EN 50200; VDE
0482-200; BS EN 50200 |
21 |
Approval |
LPCB 1469b/01 |
22 |
Cable Marking |
ERVITAL FIRE
SAFE ELECTRIC CABLE ..x.. mm² EN50200 PH120 BS 6387-CWZ 300/500V LPCB
1469b/01 YYYY @UE/@OK C€ MADE IN TURKEY
CCCCC mt |