Fluke 975V AirMeter™
4,010.05SAR
4,010.05SAR
Ex Tax: 3,487.00SAR
The Fluke 975 AirMeter test tool raises indoor air monitoring to the next level by combining five powerful tools in one, rugged and easy-to-use handheld device. Use the Fluke 975 to optimize HVAC ventilation settings for ASHRAE 62 recommendations, to actively monitor conditions that promote a productive environment, and quickly and accurately address occupant comfort complaints the first time. The Fluke 975 measures:
- Temperature
- Velocity
- Humidity
- CO2
- CO
Use the Fluke 975 AirMeter test tool to:
- Respond to comfort-related calls from occupants.
- Verify the operation of building HVAC control systems.
- Determine whether adequate ventilation exists.
- Monitor air flow and velocity.
- Test for dangerous carbon monoxide leaks.
- Perform duct traversals.
- Optimize HVAC systems to manage energy costs
![]() | The Fluke 975 offers an unparalleled featureset for HVAC and facilities technicians, helping them work more quickly and accurately, with the ease of use and durability customers expect from a Fluke meter. |
|
*Included with Fluke 975V, optional with Fluke 975
Measured Specifications Temperature Range -20°C to 50°C (-5°F to 122°F) Display resolution 0.1°C (0.1°F) Accuracy ±0.9°C / ±1.62°F from 40°C to 60°C
±0.5°C / ±1.00°F from 5°C to 40°C
±1.1°C / ±1.98°F from -20°C to 5°CRelative humidity Range 10% to 90% RH, non-condensing Display Resolution 1% Accuracy ±2% RH (10% RH to 90% RH) Air velocity Range 50.0 fpm to 3000 fpm
0.25 m/sec to 15 m/secDisplay Resolution 1 fpm (0.005 m/sec) Accuracy ±4% or 4 fpm1
±4% or 0.02 m/sec1 whichever is greater1. Accuracy specification only valid for velocity readings above 50 fpm. C0 Range 0 to 500 ppm Display Resolution 1 ppm Accuracy ±5% or ±3 ppm, whichever is greater, @ 20°C and 50% RH C02 Range 0 to 5000 ppm Display Resolution 1 ppm Accuracy Warm up time 1 min (5 minutes for full specification) 2.75% + 75 ppm Calculated Specifications Dew point temperature Range -44°C to 50°C, (-47°F to 122°F) Display Resolution 0.1°C (0.1°F) Accuracy ±1°C when temp: -20°C to 50°C RH: 40% to 90%
±2°C when temp: -20°C to 50°C RH: 20% to 40%
±4°C when RH: 10% to 20%Wet bulb temperature Range -16°C to 50°C, (3°F to 122°F) Display Resolution 0.1°C, (0.1°F) Accuracy ±1.2°C when RH: 20% to 90% temp: -20°C to 60°C
±2.1°C when RH: 10% to 20%Volume flow rate (in a duct) Range 0 to 3,965 M3/m, (0 to 140,000 cfm) Display Resolution 0.001 M3/min, (1 cfm) Accuracy N/A: The volume flow calculation will be a simple average of the data points times the duct area % outside air (based on temperature) Range 0 to 100% Display Resolution 0.1 % outside air (based on CO2) Range 0 to 100% Display Resolution 0.1% N/A General Specifications Operating and storage temperature -20°C to 50°C (-4°F to 122°F) Humidity 10% to 90% (non-condensing) Altitude Up to 2000 m (6562 ft) Shock and vibration MIL-PRF-28800F: Class 2 Multi-language interface English, French, Spanish, Portuguese and German Battery Rechargeable Li-Ion (primary), three-AA (backup) Data logging 25,000 records (continuous), 99 records (discrete) Warranty Two-years