Fluke CNX 3000 HVAC System
Fluke CNX 3000 HVAC System
A complete wireless measurement system that lets you make primary measurements on your multimeter while simultaneously viewing measurements from the remote current and temperature modules.
Overview
The CNX 3000 HVAC System is part of the Fluke team of
wireless troubleshooting tools.
Connect
the CNX a3000 AC Wireless Current Clamp Module to your test point, and view the
results up to 20 meters away on the CNX Wireless Multimeter. Plus, you can
connect the CNX t3000 K-type wireless temperature module and view remote
temperature measurements. You’ll save time, with less run-around collecting
multiple measurements. Use multiple modules for measurements on three-phase
systems. Or use as a stand-alone measurement tool or combine with other CNX
modules as a system for multiple measurements. From short distances, you can
even view readings from modules through closed electrical panels. Plus no more
writing down data as the CNX remote modules captures up to 65,000 sets of time
stamped min/max/avg readings, using the optional PC adapter. CNX wireless test
tools also offer increased safety by letting you view readings in a separate
location from the test point. Now you can take readings on moving machinery,
with only the measurement module in harm’s way.
Features
The CNX 3000 HVAC System provides measurement of all common electrical and temperature parameters.
The CNX 3000 Wireless Multimeter offers:
- True-RMS AC and DC voltage measurements to 1000V
- True-RMS AC and DC current with 0.01 mA resolution
- Continuity, resistance, diode test, capacitance and frequency measurements
- MIN/MAX Recording
- CAT III 1000 V; CAT IV 600 V; IP54
The CNX t3000 K-Type Wireless Temperature Module
offers:
- Temperature measurements from -200 °C to 1372 °C
- ± 0.5% accuracy
- Memory recording up to 65,000 readings
- Backlit LCD display; IP42 with thermocouple attached
The CNX a3000 AC Wireless Current Clamp Module
provides:
- True-RMA AC current measurements to 400 A
- 2% accuracy to 100Hz, 2-1/2% accuracy to 500Hz
- Memory recording up to 65,000 readings
- iFlex current probe allows you to get into tight, awkward spaces
- Backlit LCD display
- CAT III 600 V; IP42
Using the optional PC adapter, the CNX wireless troubleshooting system can track up to 10 measurement modules simultaneously, with results sent to a PC for further analysis.
Specifications
CNX 3000 Wireless Multimeter
For all specifications:
accuracy is specified for one year after calibration, at operating temperatures
of 18 °C to 28 °C, with relative humidity at 0 % to 90 %. Accuracy
specifications take the form of ± ([ % of Reading ] + [ Number of least
significant digits ]).
Detailed Specifications |
|||
AC voltage |
|||
Range ¹ |
Resolution |
Accuracy ² ³ |
|
45 Hz to 500 Hz |
500 Hz to 1 kHz |
||
600.0 mV |
0.1 mV |
1.0 % + 3 |
2.0 % + 3 |
6.000 V |
0.001 V |
||
60.00 V |
0.01 V |
||
600.0 V |
0.1 V |
||
1000 V |
1 V |
||
¹ All AC voltage ranges are
specified from 1 % of range to 100 % of range. |
DC Voltage, Continuity, Resistance, Diode Test and Capacitance |
|||
Function |
Range |
Resolution |
Accuracy |
mV |
600.0 mV |
0.1 mV |
0.09 % + 2 |
V |
6.000 V |
0.001 V |
0.09 % + 2 |
60.00 V |
0.01 V |
||
600.0 V |